| Management number | 204413835 | Release Date | 2025/10/17 | List Price | $563.64 | Model Number | 204413835 | ||
|---|---|---|---|---|---|---|---|---|---|
| Category | |||||||||
SurgeX UPS-1000-OL Online/Double Conversion UPS 1000VA, 2RU
SurgeX's UPS-1000-OL Standalone UPS solutions deliver clean continuous power, via online double conversion technology, to ensure the safe shutdown of equipment in the event of an outage. All incoming power is converted from AC to DC and then back to AC. If the main power is interrupted, the batteries are still holding up the incoming DC supply to the inverter, so the load continues to be supplied with absolutely no interruption whatsoever. The zero transfer time guarantees mission critical equipment remains up and running.
Key Features
Technical Specifications
Power Rating
1000 VA / 900 W
Topology
On-Line Double Conversion
Heat Dissipation (BTU/Hour)
520 at 100% Load
Input Voltage
(Nominal)
Range
100-120 VAC; 90-150 VAC
Input Frequency
50/60 Hz ±4 (Auto Sense on Start-Up)
Input Power Factor
>0.95
Input Current THD
<9.0%
Efficiency
>84.0%
Output Voltage
120 VAC (Default) 100/110/115 VAC (Selectable)
Output Current
8.3 A (Default) 8.0/8.2/8.3 A (Selectable)
Voltage Regulation
±1.0%
Overload Online Mode
100-105%: Continuous; Warning Only; 105-130%: 2 Minutes; 130-200%: 10 Seconds; >200%: 250 Milliseconds
Overload Battery Mode
100-105%: Continuous; Warning Only; 105-130%: 10 Seconds; >130%: 250 Milliseconds
Overload Bypass Mode
100-110%: Continuous; Warning Only; 110-120%: 30 Minutes; 120-130%: 10 Minutes; >130%: 1 Minute
Battery Voltage (Float / Nominal)
27.4/24.0 VDC
Charger Current
1.0 A
Backup Time (Full Load)
>3.5 Minutes
Communications Interface
USB / RS-232
Shipping Weight
37.0 lbs. / 16.8 kg.